2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz
2.2.5 the entire set of action time (including the inherent time of the relay)
Time of motion of a fast moving segment:
1.2 times the value of the entire set of measurement, not more than 50ms
2.2.6 transient transcendence
No more than 5%
2.2.7 og measurement loop accuracy
Measurement and control device for installing special measurement sub module:
Current, voltage: 0.2
Power and electric degree: 0.5
2.3 insulation performance
2.3.1 insulation resistance
Device for charged and uncharged part and a casing and electrical contact of the circuit between the open circuit voltage of 500V megohm meter measuring the insulation resistance value, normal test atmospheric conditions, the circuits of each class of insulation resistance should not be less than 100m ohm.
2.3.2 medium strengthUnder normal test conditions, the device can withstand the frequency of 50Hz, voltage 2000V lasted 1 minutes of power frequency voltage withstand test without breakdown flashover and component damage. During the test, the other circuit is connected to the ground with the other circuit when the voltage is applied.
The rotor low voltage action criterion equation is:
Kf×Vfd/125 < (P-Pt)/866
3.5 Over load protection
Generator stator winding protective reaction of load generator stator winding overload or fault caused by overcurrent caused overheating winding, discrimination protection generator winding B phase current size, when the current is higher than setting value when the delay send alarm **.
3.6 compound voltage over current protection
Generator compound voltage over-current protection is as a generator of symmetric and asymmetric short-circuit fault back-up protection, protection discriminant generator three-phase current, AC phase voltage and negative sequence voltage, when any phase current is greater than the fixed value, and AC phase voltage less than fixed value or negative sequence voltage is greater than the fixed value export protection settings have two period of time delay, a movement in solution column or splitting demagnetization, off action to stop, protection can choose to take the current memory function.
3.7 inverse time overcurrent protection
Generator anti time limit over current protection of the generator stator winding current size, the protection of the winding due to the current too large and lead to the stator winding overheating, the protection of the three-phase current size of the judge, from three parts:
2.5 mechanical properties
2.5.1 vibration
The device can withstand the vibration endurance test of the I level of 16.3 in the GB7261.
2.5.2 impact
The device can withstand the impact endurance test of the I level of 17.5 in the GB7261.
2.5.3 collision
The device can withstand the impact endurance test of the GB7261 level of I in the eighteenth chapter.
2.6 environmental conditions
A) ambient temperature: Work: -40 C ~ 85.
Storage: 25 degrees to +70 degrees Celsius, in the limit value does not apply the amount of incentive, the device does not appear irreversible change
After the temperature is restored, the device should be able to work properly.
Relative humidity: the maximum monthly average relative humidity of 90%, while the average monthly average of.
The lowest temperature is 25 DEG C and no condensation surface. When the maximum temperature of +40 degrees Celsius, the average maximum relative humidity
Degree no more than 50%.
(c) atmospheric pressure: 86 to 106kPa (relative altitude below 2km)